DR, FR, LR, ER… How to read 100G–800G interface designations and not buy the wrong module

Two 400G modules can be entirely incompatible. They may require a different fibre type, a different connector, a different number of lanes, and they will not establish a link with one another, even though both have 400G printed on the housing. The difference is carried by two or three characters in the designation: DR, FR, LR, ER. For someone who knows the convention, the module name is a complete set of information about reach, fibre type, and the number of lanes needed. For someone who does not, it is random letters and a source of costly ordering mistakes. Below is the full key to reading these designations.

The anatomy of a designation


A full interface designation consists of three parts. Take the example 400GBASE-DR4.

400GBASE-DR4
400G
the nominal interface bit rate in gigabits per second
BASE
baseband, dropped in conversation, people simply say DR4
DR
the reach class and medium type, the information that decides the selection
4
the number of parallel optical lanes, decides the cable and connector

Reading from the right: four lanes, reach class DR, bit rate 400G. Each of these three pieces of information has to match the infrastructure. A match of two out of three is not enough.

Reading the designation from the right: four lanes, reach class DR, bit rate 400G. Each of these three pieces of information has to match the infrastructure the module goes into. A match of two out of three is not enough.

The reach letters


This is the core of the designation. The letters come from the English names for reach and arrange themselves into a logical scale.

AbbreviationFromFibreApproximate reach
SRshort reachmultimodethe only MMup to 100 m
DR500 metre reachsingle-mode500 m
FRfar reachsingle-mode2 km
LRlong reachsingle-mode10 km
ERextended reachsingle-mode30–40 km
ZRoutside IEEE namingsingle-modecoherent80 km and more

Three things are worth noting about this table. SR is the only one that works on multimode fibre, and it is the most common cause of a non-working link with a seemingly correct order, because an SR module plugged into single-mode fibre will not work, and vice versa. The multimode reach additionally depends on the fibre category, because OM3 and OM4 differ significantly. ZR is a different category from the others, because SR, DR, FR, LR, and ER are intensity-modulation interfaces, that is light on or off, whereas ZR and ZR+ are coherent transmission using the phase, amplitude, and polarisation of the signal. It is a different technology, a different level of complexity, and a different price, and the name only suggests that it is the next step on the same scale. The reaches are nominal, not guaranteed, because the stated kilometres assume fibre in good condition and a small number of connectors, while a real route with a multiplexer, several connectors, and twenty splices shortens that distance. What decides is the optical power budget calculated for the specific path, not a number from a datasheet.

The digit at the end: the number of lanes


The digit says over how many parallel optical lanes the module spreads the transmission. This decides the cable and the connector, so a mistake here means the module physically will not fit into the existing infrastructure.

1no digit
One lane

Transmission over one fibre pair, a two-fibre connector of the LC type or similar. This is how most FR, LR, and ER interfaces work.

4
Four lanes, two possibilities

With DR4 the four lanes run over four separate fibre pairs, requiring a multi-fibre cable with an MPO or MTP connector. With FR4 and LR4 the four lanes are multiplexed onto different wavelengths and run over one fibre pair with a two-fibre connector.

8
Eight lanes

Typically with 800G, requires an eight-fibre or sixteen-fibre cable with an MPO connector.

The most important distinction in the whole article

A DR4 module and an FR4 module have the same speed and the same number of lanes in the name, but the first needs eight fibres and the second two. Ordering one instead of the other means either unused infrastructure or no way to connect.

This distinction between physical parallelism and wavelength multiplexing is the most important one in the whole article in practice. A DR4 module and an FR4 module have the same speed and the same number of lanes in the name, but the first needs eight fibres and the second two. Ordering one instead of the other means either unused infrastructure or no way to connect.

The most common designations in practice

100G
DesignationFibreReachFibres
100GBASE-SR4multimodeup to 100 m8
100GBASE-DRsingle-mode500 m2
100GBASE-FRsingle-mode2 km2
100GBASE-LR4single-mode10 km2
100GBASE-ER4single-mode30–40 km2
100G ZRsingle-mode80 km and more2, coh.
400G
DesignationFibreReachFibres
400GBASE-SR8multimodeup to 100 m16
400GBASE-DR4single-mode500 m8
400GBASE-FR4single-mode2 km2
400GBASE-LR4single-mode10 km2
400GBASE-ER4single-mode30–40 km2
400G ZRsingle-modeup to 120 km2, coh.
400G OpenZR+single-mode600 km and more2, coh.
800G
DesignationFibreReachFibres
800GBASE-SR8multimodeup to 100 m16
800GBASE-DR8single-mode500 m16
800GBASE-2FR4single-mode2 km4
800G ZR and ZR+single-modefrom 80 km2, coh.

At 800G a convention with a numeric prefix appears, such as 2FR4. It means two independent FR4 interfaces in a single module housing, which allows an 800G port to be split into two 400G links.

Ordering traps

⚠
Both ends of the link must have the same interface

A DR4 module will not establish a link with FR4, even though both are 400G and both have a four in the name. They work on different wavelengths and in a different lane architecture. The same rule applies to LR4 and ER4.

⚠
Breakout requires compatibility on both sides

You can split a 400G DR4 port into four 100G DR links, but only if the device supports breakout mode and there are 100G DR modules on the appropriate cable on the other side. Simply buying DR4 does not give you breakout.

⚠
MPO is not a single connector type

It comes in eight-, twelve-, sixteen-, and twenty-four-fibre variants, with different polarity and end-face polish. An MPO-12 cable will not replace MPO-16, even though the connector looks similar.

⚠
Nominal reach is not design reach

An LR4 module with a reach of 10 km on a nine-kilometre route with a multiplexer and eight connectors may not close the power budget. Always calculate the budget for the specific path.

⚠
ER and ZR are different worlds in price

Moving from ER4 to ZR is not the next step in reach, but a change of technology to coherent, with the corresponding difference in price. On a 45 km route, first check whether an ER module with a better budget will handle it.

⚠
Manufacturers' naming is sometimes their own

Alongside the IEEE designations there are trade names and extended variants, such as LR4 Lite with a reduced reach or ER4 with a reach of 40 km instead of 30. When ordering, the datasheet of the specific model decides, not the abbreviation alone.

A checklist before ordering

What fibre type is on the route: single-mode or multimode, and if multimode, what category
How many fibres are available and what connectors are on the patch panel
What the real route length along the cable is
What the calculated optical power budget for this route is
What interface is on the other side of the link, exactly the same or only the same speed
Whether breakout is planned and whether the device supports it
What housing format the port supports: QSFP28, QSFP-DD, OSFP
Whether the device supports the module in the installed software version
Whether the cable and connectors are compatible with the number of lanes in the module

When you are not sure


Choosing an interface involves several variables at once, and a mistake is costly, because a module ordered for a different fibre usually cannot be used elsewhere in the network. We verify every order of GBC Photonics modules before shipping for compatibility with the customer's device and the route parameters. We code modules for the specific platform, and for multi-vendor environments we offer the SRD 5 programmer, which lets you change the compatibility configuration in the field.

FAQ

FAQ, optical interface designations

It is the reach class and medium type, that is the core of the whole designation. The letters come from the English names for reach and arrange into a scale: SR is short reach, up to 100 m on multimode fibre, DR is 500 metre reach, 500 m on single-mode, FR is far reach, 2 km, LR is long reach, 10 km, and ER is extended reach, 30 to 40 km, all on single-mode. ZR stands apart, meaning 80 km and more, but already in coherent technology. The reaches are nominal, not guaranteed, because they assume fibre in good condition and few connectors. The actual reach is decided by the optical power budget calculated for the specific path, not by a number from a datasheet.
No. Two 400G modules can be entirely incompatible, requiring a different fibre type, a different connector, and a different number of lanes, even though both have 400G printed on the housing. Both ends of the link must have exactly the same interface, because a DR4 module will not establish a link with FR4, though both are 400G and both have a four in the name. They work on different wavelengths and in a different lane architecture. The same rule applies to LR4 and ER4. When ordering, the key question is exactly which interface is on the other side of the link, not just what speed.
By the number of fibres needed, and this is the most important distinction in the whole topic in practice. The digit at the end says over how many parallel lanes the module spreads the transmission, but with a four there are two possibilities. In DR4 the four lanes run over four separate fibre pairs, so a multi-fibre cable with an MPO or MTP connector is needed, eight fibres in total. In FR4 and LR4 the four lanes are multiplexed onto different wavelengths and run over one fibre pair with a two-fibre connector, that is two fibres. A DR4 and an FR4 module have the same speed and the same number of lanes in the name, but the first needs eight fibres and the second two. Ordering one instead of the other means either unused infrastructure or no way to connect.
Because SR is the only one in this family that works on multimode fibre, while all the rest, that is DR, FR, LR, and ER, work on single-mode. It is the most common cause of a non-working link with a seemingly correct order. An SR module plugged into single-mode fibre will not work, and vice versa, a single-mode module will not work on multimode. With SR there is one more variable, because the reach depends on the multimode fibre category, and OM3 and OM4 differ significantly. That is why the first question in selection is always: exactly what fibre type is on the route, and if multimode, what category.
It is a different technology, not the next step on the same reach scale. SR, DR, FR, LR, and ER are intensity-modulation interfaces, that is light on or off. ZR and ZR+ are coherent transmission, which uses the phase, amplitude, and polarisation of the signal, giving a different level of complexity and a different price. The name suggests that ZR is simply a greater reach than ER, but it is a separate product family. The practical conclusion is that on a route of, say, 45 km it is worth first checking whether it can be handled by an ER module with a better budget, before moving to a much more expensive coherent module.
No, MPO is not a single connector type. It comes in eight-, twelve-, sixteen-, and twenty-four-fibre variants, with different polarity and a different type of end-face polish. An MPO-12 cable will not replace MPO-16, even though the connector looks very similar. That is why with a multi-lane module you have to verify that the cable and connectors match exactly the number of lanes in the module, and not assume that because the plug fits mechanically the link will work. It is one of the more common ordering traps, because the error only reveals itself when you try to connect on site.
A numeric prefix appears at 800G and denotes the number of independent interfaces in a single module housing. 2FR4 is two independent FR4 interfaces in one module, which allows an 800G port to be split into two 400G links. This is a different situation from breakout done by the device, because here the split is built into the module's construction. If you are planning breakout in another variant, for example splitting a 400G DR4 port into four 100G DR links, remember that it works only when the device supports that mode and there are appropriate modules on a breakout cable on the other side. Simply buying the module does not give you breakout.
Nine things. What fibre type is on the route and what category if multimode. How many fibres are available and what connectors are on the patch panel. What the real route length along the cable is and what the optical power budget for that path comes out to. What interface exactly is on the other side of the link, exactly the same, not just the same speed. Whether you are planning breakout and whether the device supports it. What housing format the port supports, QSFP28, QSFP-DD, or OSFP. Whether the device will support the module in the installed software version. And whether the cable and connectors match the number of lanes in the module. Choosing an interface involves several variables at once, and a mistake is costly, because a module ordered for a different fibre usually cannot be used elsewhere in the network.
Rozpocznij z nami nowy projekt!
Dziękujemy! Otrzymaliśmy Twoje zgłoszenie!
Ups! Wystąpił błąd podczas wysyłania formularza.

QSFP28 DWDM - Scalability Simplicity for DCI

Can we find a more economical solution for connecting two or more data centers over short and medium distances?
Czytaj więcej

400ZR, 800ZR, OpenZR+: What Are They and Which DCI Network Needs Them?

ZR standards are the technology that allowed companies to cut out external transponders and connect coherent optics directly to a router port. Less equipment, a lower energy bill, and more freedom when choosing partners.
Czytaj więcej

How to increase the efficiency of data center connections?

DWDM systems enable flexible and cost-effective connection of two or more data centers.
Czytaj więcej